For solar powered systems the greatest DoD (and therefore lowest SoC) will be in early morning just before the panels start creating power again. | For solar powered systems the greatest DoD (and therefore lowest SoC) will be in early morning just before the panels start creating power again. | ||
- | DoD has a **significant impact on longevity of deep cycle batteries**. | + | DoD has a **significant impact on longevity of lead deep cycle batteries**.((and, to a lesser degree, lithium batteries)) |
- | ===== effect of SoC on battery life ===== | + | |
+ | Note: This information is primarily relevant to lead-chemistry batteries. | ||
+ | ===== effect of DoD on battery life ===== | ||
How deeply one regularly discharges lead-chemistry batteries will have a **direct effect on how long the battery bank will last**.((Banks are typically replaced when they have lost 20% of their capacity)) | How deeply one regularly discharges lead-chemistry batteries will have a **direct effect on how long the battery bank will last**.((Banks are typically replaced when they have lost 20% of their capacity)) | ||
Line 24: | Line 26: | ||
| | | | | | | | | | | | | | | | | | | | | | ||
| | | | | | | | | | | | | | | | | | | | | | ||
- | | **DoD**| | + | | **DoD**| |
| 10| 90| 22.5| | | | | | | | | 10| 90| 22.5| | | | | | | | ||
| 20| 80| 45| 3000| 135| $1.93| | | 20| 80| 45| 3000| 135| $1.93| | ||
Line 60: | Line 62: | ||
==== SoC by voltage ==== | ==== SoC by voltage ==== | ||
+ | |||
+ | Note: read [[https:// | ||
100% SoC (~12.7v) is measured [[electrical: | 100% SoC (~12.7v) is measured [[electrical: | ||
Line 72: | Line 76: | ||
* intermittent heavier loads that leave the system with measured >=12.2v when that load is removed | * intermittent heavier loads that leave the system with measured >=12.2v when that load is removed | ||
- | The more challenging task is judging when to kill the circuit based on voltage **under heavier loads**. | + | The more challenging task is judging when to kill the circuit based on voltage **under heavier loads**. |
+ | |||
+ | {{ https:// | ||
+ | |||
+ | For a 200A bank 50% DoD would be 12.1v at rest, ~12.0v at C/10 (20A discharge), ~11.55v at C/5 (40A discharge), and 11.2v at C/3 (~70A discharge). | ||
+ | |||
+ | It may take experimentation with your system to see where the battery voltage rebounds after removing the heavy loads. | ||
- apply expected load | - apply expected load | ||
Line 81: | Line 91: | ||
If the battery rebounds to the desired voltage then repeat to deeper discharge. | If the battery rebounds to the desired voltage then repeat to deeper discharge. | ||
+ | An [[electrical: | ||