Line 6: | Line 6: | ||
DoD has a **significant impact on longevity of deep cycle batteries**. | DoD has a **significant impact on longevity of deep cycle batteries**. | ||
+ | |||
+ | Note: This information is primarily relevant to lead-chemistry batteries. | ||
===== effect of SoC on battery life ===== | ===== effect of SoC on battery life ===== | ||
Line 74: | Line 76: | ||
* intermittent heavier loads that leave the system with measured >=12.2v when that load is removed | * intermittent heavier loads that leave the system with measured >=12.2v when that load is removed | ||
- | The more challenging task is judging when to kill the circuit based on voltage **under heavier loads**. | + | The more challenging task is judging when to kill the circuit based on voltage **under heavier loads**. |
+ | |||
+ | {{ https:// | ||
+ | |||
+ | For a 200A bank 50% DoD would be 12.1v at rest, ~12.0v at C/10 (20A discharge), ~11.55v at C/5 (40A discharge), and 11.2v at C/3 (~70A discharge). | ||
+ | |||
+ | It may take experimentation with your system to see where the battery voltage rebounds after removing the heavy loads. | ||