This shows you the differences between two versions of the page.
Both sides previous revision Previous revision | Next revision Both sides next revision | ||
electrical:depth_of_discharge [2023/08/17 21:22] frater_secessus [knowing when SoC is 100% (fully charged)] |
electrical:depth_of_discharge [2023/08/17 21:24] frater_secessus [soft and firm charging] |
||
---|---|---|---|
Line 29: | Line 29: | ||
- | Solar is typically a moderate (or " | + | Solar is typically a moderate (or " |
- | So while we can say with confidence that a 100Ah Li battery charged at 20A to 14.0v will be ~100% SoC, the same battery charged to 14.0v at 80A might only be at 75% SoC. The amp counter will probably help here during charging. | + | So while we can say with confidence that a 100Ah Li battery charged at 20A to 14.0v will be ~100% SoC, the same battery charged to 14.0v at 80A might only be at 75% SoC. The amp counter will probably help here during charging |