 Lead-acid chemistries prefer light cycling and full recharge between those cycles.  Lead-acid batteries are traditional cycled to [[electrical:depth_of_discharge|50% depth of discharge]] because it offers a balance between duty life (years between failure) and bank size.(("dead lead"))  Pulling the bank below 50% DoD in emergnecies will not automatically cause damage //assuming a full charge is accomplished ASAP//. Lead-acid chemistries prefer light cycling and full recharge between those cycles.  Lead-acid batteries are traditional cycled to [[electrical:depth_of_discharge|50% depth of discharge]] because it offers a balance between duty life (years between failure) and bank size.(("dead lead"))  Pulling the bank below 50% DoD in emergnecies will not automatically cause damage //assuming a full charge is accomplished ASAP//.
  
-This article is about the intentional and chronic depletion of lead-acid banks below the 50% mark, **followed by vigorous recharging**.+This article is about the intentional and chronic depletion of lead-acid banks below the 50% mark, **followed by vigorous recharging**.  This might be desirable when: 
 + 
 +  * reducing the weight impact of lead banks 
 +  * one wants to make use of old/damaged batteries whose capacity has declined
  
 ===== how low can we go? ===== ===== how low can we go? =====
Line 17: Line 20:
 ===== limiting the damage ===== ===== limiting the damage =====
  
-Deep cycles generally extend the amount of time for a battery to complete Absorption.  +Deep cycling generally extends the amount of time for a battery to complete Absorption.  
  
   * get power back into the battery ASAP after deep discharge;  drive for [[electrical:12v:alternator|alternator charging]] or run a [[electrical:generator|generator]] to get bulk stage going.  Solar alone //might// be sufficient but it might require meaningful [[electrical:solar:overpaneling|overpaneling]].     * get power back into the battery ASAP after deep discharge;  drive for [[electrical:12v:alternator|alternator charging]] or run a [[electrical:generator|generator]] to get bulk stage going.  Solar alone //might// be sufficient but it might require meaningful [[electrical:solar:overpaneling|overpaneling]].  
-  * increase Absorption time, or even set Vfloat == Vabs. + 
-  * if floodedkeep a close watch on water levels+ 
 +===== increasing effective Absorption duration ===== 
 + 
 +While you may not be able to increase the //actual// Absorption duration,((as when the controller setpoint is maxxed out)) you can achieve a similar effect with one or more of these techniques:  
 + 
 + 
 +  * if duration setpoint is maxxed then **set Vfloat == Vabs** Absorption duration will effectively be "until the sun goes down".   
 +  * **charge at a lower current** (charging minimum).  While [[opinion:frater_secessus:charging_faster|overall charging will take about the same amount of time]]Bulk's share of that time will increase and [[electrical:12v:charging#absorption|Absorption will take somewhat less time]]. 
 +  * **charge at a higher voltage** (Vabs), this will decrease Absorption duration.  Keep a close watch on water levels for flooded batts, and also mind the max allowable voltage for AGM/Gel. 
  
  
  