This shows you the differences between two versions of the page.
Both sides previous revision Previous revision Next revision | Previous revision Next revision Both sides next revision | ||
electrical:solar:nonessential [2020/07/08 13:17] frater_secessus [uses for opportunity loads] |
electrical:solar:nonessential [2020/10/11 19:48] 127.0.0.1 external edit |
||
---|---|---|---|
Line 21: | Line 21: | ||
**The best time to run non-essential loads is when there is surplus current** over what battery charging needs. | **The best time to run non-essential loads is when there is surplus current** over what battery charging needs. | ||
- | Opportunity loads should not be applied during [[electrical: | + | Opportunity loads should not be applied during [[electrical: |
+ | |||
+ | **PWM controllers** will make [[electrical: | ||
===== timing opportunity loads ===== | ===== timing opportunity loads ===== | ||
+ | |||
+ | The trickiest part of running opportunity loads is running them at the right time so battery charging is not affected. | ||
+ | |||
+ | |||
+ | ==== manual model ==== | ||
+ | |||
+ | |||
You can start the loads **manually** (ie, start using the power when you have extra). | You can start the loads **manually** (ie, start using the power when you have extra). | ||
Line 35: | Line 44: | ||
Read the documentation and ask their techs questions before taking this $$$ approach. | Read the documentation and ask their techs questions before taking this $$$ approach. | ||
- | Related: | + | Related: |
+ | |||
+ | * you can also build a Pi or similar that talks to the controller over its communication port/ | ||
+ | * [[https:// | ||
==== diversion controller ==== | ==== diversion controller ==== | ||
Line 61: | Line 74: | ||
In this approach the LVD is set just below Vfloat as above, but activation of the loads is delayed by some amount of time. Observation of the system during charging will suggest how long it normally takes takes charging amperage to drop off (ie, when the system has surplus current). | In this approach the LVD is set just below Vfloat as above, but activation of the loads is delayed by some amount of time. Observation of the system during charging will suggest how long it normally takes takes charging amperage to drop off (ie, when the system has surplus current). | ||
- | Suggested delay for conservative opportunity loading == the time from [passing Vlvr setpoint during Bulk] to [completed charging].((settling to Float)). | + | Suggested delay for conservative opportunity loading == the time from [passing Vlvr setpoint during Bulk] to [completed charging].((settling to Float)). |
Line 72: | Line 85: | ||
==== LVD + timer - eternal Absorption ==== | ==== LVD + timer - eternal Absorption ==== | ||
- | This setup avoids timer juggling/ | + | This setup avoids timer juggling/ |
- [[electrical: | - [[electrical: | ||
Line 78: | Line 91: | ||
- set the LVD to just under Vabs, set the timer to the Absorption duration | - set the LVD to just under Vabs, set the timer to the Absorption duration | ||
+ | Similar to the above, this setup looks like: [LVD or controller LOAD output] –> timer –> relay –> load | ||
===== uses for opportunity loads ===== | ===== uses for opportunity loads ===== |