 ===== Series-Parallel ===== ===== Series-Parallel =====
  
-FIXME+Consider this scenario: 
 + 
 + 
 +  * 4 panels  
 +    * 150w 
 +    * Vmp == 19v 
 +    * Voc == 22.8 
 +    * Imp == 7.9A 
 +  * MPPT controller with 60v maximum input voltage 
 + 
 +A fully-series configuration ([[electrical:12v:parallel_serial|1p4s]]) would have a **Voc of 91.2v**, greatly exceeding the controller's input spec of 60v, and it's common to want to have 20% voltage headroom above Voc.  
 + 
 +A fully-parallel configuration (4p1s) would require 3x 2-into-1 MC4 adapters or 1x 4-into-1 adapter.  The wiring from the array would need to carry 30A+ to the controller,  necessitating heavier wiring that would cost more and might not even fit the controller terminals.  It might be unable to charge at all under extreme low-light conditions.  
 + 
 +A compromise might be series-parallel array (2p2s) with 45.6Voc and ~16A.  This would require 1x 2-into-1 MC4 adapter to combine the two serial strings.   
  
  