| - | Lead chemistries require a minimum charge rate to stay healthy. | + | Lead chemistries require a minimum charge rate to stay healthy. |
| * 0.2C for AGM | * 0.2C for AGM | ||
| Line 53: | Line 53: | ||
| ==== charging time available ==== | ==== charging time available ==== | ||
| - | If you have solar and will be on shore power for more than one day then a simple converter that charges at the batteries' | + | If you have solar and will be on shore power for more than one day then **a simple converter that charges at the batteries' |
| If you do not have solar or will be on shore power for only one overnight then we need a three-stage (" | If you do not have solar or will be on shore power for only one overnight then we need a three-stage (" | ||
| Line 85: | Line 85: | ||
| " | " | ||
| - | If loads are run off the converter in the daytime the converter will just be supporting the solar yield and can be rather small. | + | If loads are run off the converter in the daytime the converter will just be supporting the solar yield and can be rather small. |