 ====== C notation ====== ====== C notation ======
  
-Battery capacity in Amp-hours is written as **C**.  This notation is most useful when talking about charging/discharging rates +**Battery capacity** in Amp-hours is written as **C**.  100Ah, for example.
  
-Note:  most deep cycle manufacturer's rate capacity at C/20, due to Peukert effect.+C notation can also be used to describe the **relative amount of current** charging/discharging battery bank. For example a 50A load on a 100Ah bank would be C/2 (100/2 == 50).((technically C/20/2but that form is rarely seen outside formal documents))It may also be written as 0.5C.((decimal vs. fractional expression, can be used interchangably))
  
  
 +Note:  most deep cycle manufacturer's rate capacity at C/20, due to Peukert effect on lead chemistries (see below).((Lithium doesn't not have a significant Peukert effect.  Capacity measured by C/20 and by amp-counting will be nearly identical)).  In other words, a 100Ah battery will deliver 100A with a 5A load over 20 hours.
 +
 +
 +
 +===== Examples =====
  
-Examples: 
 If you have a 200AH battery bank then C = 200AH. If you have a 200AH battery bank then C = 200AH.
  
Line 13: Line 17:
  
 If the manufacturer recommends minimum charging at C/10 the rate should be at or above 20A (200/10). \\  If the manufacturer recommends minimum charging at C/10 the rate should be at or above 20A (200/10). \\ 
-Note: the **usual charge rate** for deep cycle batteries is C/10.  Sometimes manufacturers express that [[electrical:12v:charging|Absorption stage]] is complete((and therefore Float should commence)) when the bank is holding Vabs and charging current has dropped to C/100 or C/200. 
  
 If the manufacturer recommends max //discharge// (load) be 3C the rate should be at or below 600A (3x200). \\  If the manufacturer recommends max //discharge// (load) be 3C the rate should be at or below 600A (3x200). \\ 
  
 +If the manufacturer says that [[electrical:12v:charging|Absorption stage]] is complete when charging current has dropped to C/100 or C/200 then the current to watch for would be 2A (200/100) or 1A (200/200).
 +
 +===== other than 20hr rates =====
 +
 +Because of the Peukert effect, lead bank //measured// capacities are strongly affected by dicharge rate. Sample data below is for flooded lead acid.((Due to lower internal resistance AGM is less affected by discharge rate and lithium is barely affected at all.))  C/20 capacity is multiplied by the factor below to find projected capacity at given discharge rates.
 +
 +Example:  our battery is rated at 100Ah when drained at 5A over 20 hours.  If it is drained at 20A in 5 hours it will have an observed capacity of 70Ah (100Ah x .7).
  
  
 +1 Hour = .3 \\
 +2 Hour = .5 \\
 +3 hour = .6 \\
 +4 hour = .65 \\
 +5 hour = .7 \\
 +6 hour = .75 \\
 +8 hour = .8 \\
 +10 hour = .85 \\
 +12 hour = .9 \\
 +16 hour = .95 \\
 +20 hour = 1 \\
 +24 hour = 1.05 \\
 +36 hour = 1.1 \\
 +72 hour = 1.25 \\
 +100 hour = 1.30((vhttps://www.solarpaneltalk.com/forum/off-grid-solar/batteries-energy-storage/11731-peukert-law-batteries-and-you#post11731))