User Tools

Site Tools


electrical:12v:battery_capacity

This is an old revision of the document!


C notation

Battery capacity in Amp-hours is written as C. This notation is most useful when talking about charging/discharging rates.

Note: most deep cycle manufacturer's rate capacity at C/20, due to Peukert effect. In other words, a 100Ah battery will deliver 100A with a 5A load. See table at bottom for other load levels.

Examples

If you have a 200AH battery bank then C = 200AH.

If the manufacturer recommends max charging at C/5 the rate should be at or below 40A (200/5).

If the manufacturer recommends minimum charging at C/10 the rate should be at or above 20A (200/10).

If the manufacturer recommends max discharge (load) be 3C the rate should be at or below 600A (3×200).

If the manufacturer says that Absorption stage is complete when charging current has dropped to C/100 or C/200 then the current to watch for would be 2A (200/100) or 1A (200/200).

other than 20hr rates

For other than C/20 loads1):

1 Hour = .3
2 Hour = .5
3 hour = .6
4 hour = .65
5 hour = .7
6 hour = .75
8 hour = .8
10 hour = .85
12 hour = .9
16 hour = .95
20 hour = 1
24 hour = 1.05
36 hour = 1.1
72 hour = 1.25
100 hour = 1.302)

1)
flooded
2)
vhttps:www.solarpaneltalk.com/forum/off-grid-solar/batteries-energy-storage/11731-peukert-law-batteries-and-you#post11731))
electrical/12v/battery_capacity.1602460085.txt.gz · Last modified: 2020/10/11 19:48 by 127.0.0.1