   * Multiple non-communicating controllers set up to trigger Float from endAmps((trailing amps)) may enter float early since they are providing only some of the charging current.   * Multiple non-communicating controllers set up to trigger Float from endAmps((trailing amps)) may enter float early since they are providing only some of the charging current.
   * Multiple sources may inadvertently exceed the bank's recommended charging current, or your preferred current.  Example:  a lithium battery wants 50A max but each charging source can make 30A.  This might result in overcurrent (60A) during Bulk.     * Multiple sources may inadvertently exceed the bank's recommended charging current, or your preferred current.  Example:  a lithium battery wants 50A max but each charging source can make 30A.  This might result in overcurrent (60A) during Bulk.  
-  * theoretical:  low-frequency PWM controllers in parallel with MPPT controllers may confuse the MPPT with an unstable reference voltage. +  * theoretical:  low-frequency PWM controllers in parallel with MPPT controllers may confuse the latter with an unstable reference voltage. 
  
  
  