* not charging at [[electrical:solar:charge_controller_setpoints|manufacturer-recommended Absorption voltage]] (Vabs) to reverse normally-occurring ("soft") sulfation. This is most commonly caused by [[electrical:12v:alternator|isolator-only]] charging since the house bank is being charged at ((or slightly below)) alternator voltage. \\ Less commonly, [[electrical:solar|Solar]]-only charging can cause this problem if the [[electrical:solar:sizing|battery capacity is too great for the solar output]].((http://support.rollsbattery.com/support/solutions/articles/5964-battery-sulfation)) | * not charging at [[electrical:solar:charge_controller_setpoints|manufacturer-recommended Absorption voltage]] (Vabs) to reverse normally-occurring ("soft") sulfation. This is most commonly caused by [[electrical:12v:alternator|isolator-only]] charging since the house bank is being charged at ((or slightly below)) alternator voltage. \\ Less commonly, [[electrical:solar|Solar]]-only charging can cause this problem if the [[electrical:solar:sizing|battery capacity is too great for the solar output]].((http://support.rollsbattery.com/support/solutions/articles/5964-battery-sulfation)) |
* not holding Vabs for [[electrical:severe_battery_use#increasing_effective_absorption_duration|sufficient duration]] so that absorption current drops to manufacturer-recommended levels. [[electrical:generator#charging_batteries|Generator-]] or [[electrical:12v:b2b|DC-DC charging]] can cause this unless the charger runs the necessary number of hours it takes to complete Absorption. | * not holding Vabs for [[electrical:severe_battery_use#increasing_effective_absorption_duration|sufficient duration]] so that absorption current drops to manufacturer-recommended levels. [[electrical:generator#charging_batteries|Generator-]] or [[electrical:12v:b2b|DC-DC charging]] can cause this unless the charger runs the necessary number of hours it takes to complete Absorption. |
* discharging too deeply. Maximum discharge is typically limited to 50% [[electrical:depth_of_discharge|depth of discharge]]. | * discharging too deeply. Discharge with lead-chemistries is typically limited to 50% [[electrical:depth_of_discharge|depth of discharge]] as a compromise between cycle life and bank size. |
* allowing the cells to get low on distilled water. Check them 1x/month or so until you learn their personality. | * allowing the cells to get low on distilled water. Check them 1x/month or so until you learn their personality. |
| |