Lead-acid chemistries prefer light cycling and full recharge between those cycles. | Lead-acid chemistries prefer light cycling and full recharge between those cycles. | ||
- | This article is about the intentional and chronic depletion of lead-acid banks below the 50% mark. | + | This article is about the intentional and chronic depletion of lead-acid banks below the 50% mark, **followed by vigorous recharging**. |
===== how low can we go? ===== | ===== how low can we go? ===== | ||
Line 19: | Line 19: | ||
Deep cycles generally extend the amount of time for a battery to complete Absorption. | Deep cycles generally extend the amount of time for a battery to complete Absorption. | ||
- | * get power back into the battery ASAP after deep discharge; | + | * get power back into the battery ASAP after deep discharge; |
* increase Absorption time, or even set Vfloat == Vabs. | * increase Absorption time, or even set Vfloat == Vabs. | ||
* if flooded, keep a close watch on water levels | * if flooded, keep a close watch on water levels |