Line 3: Line 3:
 Lead-acid chemistries prefer light cycling and full recharge between those cycles.  Lead-acid batteries are traditional cycled to [[electrical:depth_of_discharge|50% depth of discharge]] because it offers a balance between duty life (years between failure) and bank size.(("dead lead"))  Pulling the bank below 50% DoD in emergnecies will not automatically cause damage //assuming a full charge is accomplished ASAP//. Lead-acid chemistries prefer light cycling and full recharge between those cycles.  Lead-acid batteries are traditional cycled to [[electrical:depth_of_discharge|50% depth of discharge]] because it offers a balance between duty life (years between failure) and bank size.(("dead lead"))  Pulling the bank below 50% DoD in emergnecies will not automatically cause damage //assuming a full charge is accomplished ASAP//.
  
-This article is about the intentional and chronic depletion of lead-acid banks below the 50% mark, **followed by vigorous recharging**.  This might be desirable when:+This article is about the intentional sever use of lead-acid banks by running them below the 50% mark, **followed by vigorous recharging** at maximal voltage.  This might be desirable when:
  
   * reducing the weight impact of lead banks   * reducing the weight impact of lead banks
Line 30: Line 30:
  
  
-  * if duration setpoint is maxxed then **set Vfloat == Vabs**.  Absorption duration will effectively be "until the sun goes down".  +  * if duration setpoint is maxxed then [[electrical:12v:eternal_absorption|set Vfloat == Vabs]].  Absorption duration will effectively be "until the sun goes down".  
   * **charge at a lower current** (charging minimum).  While [[opinion:frater_secessus:charging_faster|overall charging will take about the same amount of time]], Bulk's share of that time will increase and [[electrical:12v:charging#absorption|Absorption will take somewhat less time]].   * **charge at a lower current** (charging minimum).  While [[opinion:frater_secessus:charging_faster|overall charging will take about the same amount of time]], Bulk's share of that time will increase and [[electrical:12v:charging#absorption|Absorption will take somewhat less time]].
   * **charge at a higher voltage** (Vabs), this will decrease Absorption duration.  Keep a close watch on water levels for flooded batts, and also mind the max allowable voltage for AGM/Gel.    * **charge at a higher voltage** (Vabs), this will decrease Absorption duration.  Keep a close watch on water levels for flooded batts, and also mind the max allowable voltage for AGM/Gel. 