 ===== non-setpoint settings ===== ===== non-setpoint settings =====
  
-  * **Maximum charge rate:**  While maximum charge rates normally are immaterial to solar charging((lead batteries accept what they want rather than taking what they are given)), Trojan specfies a maximum of [[electrical:12v:battery_capacity|C]]/5, or 1/5th of the battery's capacity in Ah.  +  * **Maximum charge rate:**  While maximum charge rates normally are immaterial to solar charging((lead batteries accept what they want rather than taking what they are given)), Trojan specfies a maximum of [[electrical:12v:battery_capacity|C]]/5, or 1/5th of the battery's capacity in Ah for this flooded example C/3 is a common max for AGM.  Lithium max charge is typically stated as C/2 for maximum life.   
-  * **Minimum charge rate:**  not stated in our example, but typical minimum charging values are ~C/10 for lead chemistries+  * **Minimum charge rate:**  not stated in our example, but typical minimum charging values are ~C/10 for flooded lead batteries, and ~C/5 for AGM. Lithium does not have a practical minimum rate so is not damaged by weak charging.
  
  