Line 27: Line 27:
 At the start of Absorption the controller still needs near-Bulk levels of current for charging.  At the end it needs almost no current.  **Halfway through Absorption about half of the system's peak power will be available for loads.**  See the image at the top of the page for an example of how current demand drops in Absorption. At the start of Absorption the controller still needs near-Bulk levels of current for charging.  At the end it needs almost no current.  **Halfway through Absorption about half of the system's peak power will be available for loads.**  See the image at the top of the page for an example of how current demand drops in Absorption.
  
-For [[electrical:12v:lifepo4_batteries_thread|LiFePO4]] set the LVD to Vfloat; there is no actual Absorption stage _per se_ in fractional-C charging. We use these setpoints only because our traditional lead-acid controllers work that way.+For [[electrical:12v:deep_cycle_battery#lithium_chemistries|LiFePO4]] set the LVD to Vfloat; there is no actual Absorption stage _per se_ in fractional-C charging. We use these setpoints only because our traditional lead-acid controllers work that way.
  
 ===== timing opportunity loads ===== ===== timing opportunity loads =====