Line 44: Line 44:
 ==== LVD + timer ==== ==== LVD + timer ====
 {{ :electrical:solar:discretionaryTimer.png?400|}} {{ :electrical:solar:discretionaryTimer.png?400|}}
-A [[http://amzn.to/2pN3O9o|12v timer]] could give the system a chance to make some progress in Absorption before starting up opportunity loads.  +A [[http://amzn.to/2pN3O9o|12v timer]] could give the system a chance to make some progress in Absorption before starting up opportunity loads.  If mistimed or overly heavy loads applied, Absorption duration could be affected. 
  
  
Line 57: Line 57:
  
 This setup looks like:  [LVD or controller LOAD output] --> timer --> relay --> load This setup looks like:  [LVD or controller LOAD output] --> timer --> relay --> load
 +
 +==== LVD + timer - eternal Absorption ====
 +
 +This setup avoids timer juggling/estimation and does not affect Absorption charging.
 +
 +  - set Vfloat to Vabs
 +  - observe measure how long Absorption actually takes to drop to [[electrical:solar:charge_controller_setpoints|endAmps]] on your system
 +  - set the LVD to just under Vabs, set the timer to the Absorption duration
  
  