===== when to run opportunity loads ===== | ===== when to run opportunity loads ===== | ||
- | The optimal time to run loads is when there is **power available in excess of battery charging requirements**. | + | The optimal time to run loads is when there is **power available in excess of battery charging requirements**. When done at the right time, the loads are effectively run [[electrical: |
With **lead** this means **during Float**, or **in late Absorption** when charge current acceptance has fallen enough that the system can run the loads //and still maintain the Absorption voltage setpoint// | With **lead** this means **during Float**, or **in late Absorption** when charge current acceptance has fallen enough that the system can run the loads //and still maintain the Absorption voltage setpoint// | ||
Line 25: | Line 25: | ||
There is a little more wiggle room with [[electrical: | There is a little more wiggle room with [[electrical: | ||
- | * the bank has reached the intended charge state | + | * the bank has reached the intended charge state; or |
- | * or any time the bank can be // | + | * any time the bank can be // |