Line 22: | Line 22: | ||
+ | ==== theory ==== | ||
- | **Example: | + | Consider the image to the right.((The image is that of a different PV-related configuration but it works for our purposes.)) The smaller/ |
The larger/ | The larger/ | ||
The striped area is the peak power " | The striped area is the peak power " | ||
Line 38: | Line 39: | ||
* you spend time in partial shade | * you spend time in partial shade | ||
* you want to use a smaller controller instead of jumping up to the next size. Example, 43A max output and your choices are 40A or 60A controllers. | * you want to use a smaller controller instead of jumping up to the next size. Example, 43A max output and your choices are 40A or 60A controllers. | ||
+ | |||
+ | |||
+ | ==== example ==== | ||
+ | |||
+ | Let's say you want to adhere to Victron' | ||
+ | |||
+ | * 500w / 14.2v = 35.2A. | ||
+ | * 35.2A on a 30A MPPT is 17.3% overpaneled: | ||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||