Line 93: Line 93:
  
 **Example:​** ​ You need 100AH x 1 day, so your bank will be 200AH cycled 50% each day. \\  **Example:​** ​ You need 100AH x 1 day, so your bank will be 200AH cycled 50% each day. \\ 
-**Example:​** ​ [[electrical:​12v:​lifepo4_batteries_thread|LiFePO4]] can be drained down to 80%-90% DoD so you would need only 110AH of rated capacity with that chemistry. 120AH if you are conservative.+**Example:​** ​ [[electrical:​12v:​deep_cycle_battery#​lithium_chemistries|LiFePO4]] can be drained down to 80%-90% DoD so you would need only 110AH of rated capacity with that chemistry. 120AH if you are conservative.
  
  