User Tools

Site Tools


electrical:severe_battery_use

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
Next revision Both sides next revision
electrical:severe_battery_use [2019/08/21 22:03]
frater_secessus [Intentionally severe battery use]
electrical:severe_battery_use [2021/05/05 10:55]
frater_secessus [increasing effective Absorption duration] added flloat
Line 1: Line 1:
 ====== Intentionally severe battery use ====== ====== Intentionally severe battery use ======
  
-Lead-acid chemistries prefer light cycling and full recharge between those cycles.  Infrequent excursions below the [[electrical:depth_of_discharge|50% depth of discharge]] norm will not cause much damage assuming a full charge is accomplished ASAP afterwards.+Lead-acid chemistries prefer light cycling and full recharge between those cycles.  Lead-acid batteries are traditional cycled to [[electrical:depth_of_discharge|50% depth of discharge]] because it offers a balance between duty life (years between failure) and bank size.(("dead lead"))  Pulling the bank below 50% DoD in emergnecies will not automatically cause damage //assuming a full charge is accomplished ASAP//.
  
-This article is about the intentional and chronic depletion of lead-acid banks below the 50% mark, **followed by vigorous recharging**.+This article is about the intentional severe use of lead-acid banks by running them below the 50% mark, **followed by vigorous recharging** at maximal voltage This might be desirable when: 
 + 
 +  * reducing the weight impact of lead banks 
 +  * one wants to make use of old/damaged batteries whose capacity has declined
  
 ===== how low can we go? ===== ===== how low can we go? =====
Line 17: Line 20:
 ===== limiting the damage ===== ===== limiting the damage =====
  
-Deep cycles generally extend the amount of time for a battery to complete Absorption.   
  
-  * get power back into the battery ASAP after deep discharge;  drive for alternator charging or run a generator to get bulk stage going  +  * get power back into the battery ASAP after deep discharge;  drive for [[electrical:12v:alternator|alternator charging]] or run a [[electrical:generator|generator]] to get bulk stage going.  Solar alone //might// be sufficient but it might require meaningful [[electrical:solar:overpaneling|overpaneling]].   
-  * increase Absorption time, or even set Vfloat == Vabs. +  * fully charge lead-chemistry batteries as often as possible 
-  * if floodedkeep a close watch on water levels+ 
 + 
 +===== increasing effective Absorption duration ===== 
 + 
 +Deep cycling generally extends the amount of time for a battery to complete Absorption. At some you may run into the controller's maximum Absorption duration.  While you may not be able to increase the //actual// duration,((as when the controller setpoint is maxxed out)) you can achieve a similar effect with one or more of these techniques:  
 + 
 + 
 +  * if duration setpoint is maxxed then [[electrical:12v:eternal_absorption|set Vfloat == Vabs]] Absorption duration will effectively be "until the sun goes down".   
 +  * **charge at a lower current** (charging minimum).  While [[opinion:frater_secessus:charging_faster|overall charging will take about the same amount of time]]Bulk's share of that time will increase and [[electrical:12v:charging#absorption|Absorption will take somewhat less time]]. 
 +  * **Absorb at a higher((but still manufacturer-sanctioned)) voltage** (Vabs), this will decrease Absorption duration.  Keep a close watch on water levels for flooded batts, and also mind the max allowable voltage for AGM/Gel. 
 +  * **Float at a higher((but still manufacturer-sanctioned)) voltage** (Vfloat).   
 +  * [[electrical:12v:alt_and_solar|supplement]] solar charging with another charging source during Bulk, allowing more time for solar to finish absorption.
  
  
  
electrical/severe_battery_use.txt · Last modified: 2024/03/30 21:42 by frater_secessus