This shows you the differences between two versions of the page.
Both sides previous revision Previous revision Next revision | Previous revision | ||
electrical:12v:battery_capacity [2020/05/13 15:52] frater_secessus [C notation] |
electrical:12v:battery_capacity [2025/06/24 19:12] (current) frater_secessus [C notation] |
||
---|---|---|---|
Line 1: | Line 1: | ||
====== C notation ====== | ====== C notation ====== | ||
- | Battery capacity in Amp-hours is written as **C**. | + | **C** notation is used to express the relationship of a bank's capacity to charge/ |
- | Note: most deep cycle manufacturer' | + | This relationship can also be described as a fraction; |
+ | |||
+ | Note: most deep cycle manufacturer' | ||
===== Examples ===== | ===== Examples ===== | ||
- | If you have a 200AH battery | + | Assuming |
- | If the manufacturer recommends max // | + | * If the manufacturer recommends max // |
+ | * If the manufacturer recommends minimum charging at C110 the rate should be ≤20A (200 x 0.1) | ||
+ | * If the manufacturer recommends max // | ||
+ | * If the manufacturer says that [[electrical: | ||
- | If the manufacturer recommends minimum charging at C/10 the rate should be at or above 20A (200/10). \\ | + | ===== other than 20hr rates ===== |
- | If the manufacturer recommends max //discharge// (load) be 3C the rate should be at or below 600A (3x200). \\ | + | Because of the Peukert effect, lead bank //measured// capacities are strongly affected by dicharge rate. Sample data below is for flooded lead acid.((Due to lower internal resistance AGM is less affected by discharge |
- | + | ||
- | If the manufacturer says that [[electrical: | + | |
- | + | ||
- | ===== other than 20hr rates ===== | + | |
- | For other than C/20 loads((flooded)): | + | Example: |