electrical:12v:directcharginglfp [2024/07/17 15:34] frater_secessus [testing phase] |
electrical:12v:directcharginglfp [2025/03/28 16:27] (current) frater_secessus [failures] |
=== why does C appear to decrease as bank size increases? === | === why does C appear to decrease as bank size increases? === |
| |
Current acceptance does increase with larger bank capacities but this increase can be surprisingly small: | All other things being equal, current acceptance //does// increase with larger bank capacities but this increase can be surprisingly small: |
| |
>> IF you have other things in the network with a much higher resistance than the batteries (such as using the frame as a ground return path), changing the resistance of the battery bank [ie, increasing capacity] can have only a small effect. --MechEngrSGH((https://www.rvforum.net/threads/charging-lithium-batteries-with-alternator.135673/post-1255460)) | >> IF you have other things in the network with a much higher resistance than the batteries (such as using the frame as a ground return path), changing the resistance of the battery bank [ie, increasing capacity] can have only a small effect. --MechEngrSGH((https://www.rvforum.net/threads/charging-lithium-batteries-with-alternator.135673/post-1255460)) |
=== lessons === | === lessons === |
| |
- Think twice about direct-charging banks that have 2-3x the capacity of your alternator's rating. If you need to do this use [[electrical:12v:b2b|a DC-DC charger]], external regulation, or current reduction with resistance as described elsewhere in this article. | - Think twice about direct-charging banks that have 2-3x the capacity of your alternator's rating. If you need to do this use a **properly-sized** [[electrical:12v:b2b|DC-DC charger]], external regulation, [[electrical:12v:alternator_details#thermal_switches|thermal switches]], current reduction with resistance as described elsewhere in this article, etc |
- do not idle to charge. | - do not idle to charge. |
| |
| |
==== testing phase ==== | ==== testing phase ==== |
| |
| [**Note**: this section might seem like overkill. It is intended to walk first-timers through the process in a methodical way. Experienced DIYers will already have internalized this kind of process.] |
| |
| |
For measuring charging current you can use the battery's BMS, [[electrical:12v:battery_monitor|battery monitor]], or [[https://amzn.to/3Vt8Jhh|clamp meter]]. If your vehicle has gauges for RPM and voltage you can use those. If not, you might pick up an inexpensive bluetooth OBDii dongle [[https://amzn.to/3LuvXxw|like this]] to see the values. | For measuring charging current you can use the battery's BMS, [[electrical:12v:battery_monitor|battery monitor]], or [[https://amzn.to/3Vt8Jhh|clamp meter]]. If your vehicle has gauges for RPM and voltage you can use those. If not, you might pick up an inexpensive bluetooth OBDii dongle [[https://amzn.to/3LuvXxw|like this]] to see the values. |
| |
If you are driving long enough to reach the desired state of charge (80%, 100%, whatever), you can [[electrical:12v:alternator#disabling_alternator_charging|disable alternator charging]] if desired. | If you are driving long enough to reach the desired state of charge (80%, 100%, whatever), you can [[electrical:12v:alternator#disabling_alternator_charging|disable alternator charging]] if desired. |
| |
| |
| ===== addendum: advantages of direct charging ===== |
| |
| **Cost**. If you already own a combiner then it's already paid for. If you are installing one new it would be much cheaper for the average current than DC-DC. |
| |
| Direct charging **tapers during Bulk** and DC-DC does not. In effect the combiner provides the **most current when you need it most** (batteries are low) and the least when you need it least (batteries nearly charged). This happens because when the batteries are more charged there is a smaller difference ("delta") between the alternator output and bank resting voltage (I=**V**/R again). There are some related effects: |
| |
| * **direct charging backs off when other charging sources are present**. This happens because the other charging sources affect the "resting" voltage of the bank and so the voltage delta. This can help prevent excessive charge rates. Example: 100Ah battery, 30A DC-DC and 30A solar. If both systems were running full blast the combined charging would be 60A, or [[electrical:12v:battery_capacity|0.6C]]. That is above the recommend charging current (0.5C) of most drop-ins. A combiner in the same situation might((based on my informal observations -- secessus)) drop to 15A contribution for a total of 45A. That would be 0.45C. Of course if you want to hammer at full speed all the time then DC-DC is better for that. |
| * **direct charging backs off at higher states of charge**((in the upper knee)). Cell manufacturer datasheets typically derate charging limits when the battery is >80% SoC. Engineering Explained has [[https://youtu.be/qYJk1Qljwgg?si=XPUVa3N9opEQIR0Z&t=288|a relatively-accessible video]] that explains how SoC and charge rate affect LiFePO4 degradation. |
| |
| |
| |
| |