Line 127: | Line 127: | ||
- | === backing into a minimum temperature setpoint === | + | ==== backing into a minimum temperature setpoint |
- | There are a couple steps here: | + | There are two pieces of information needed |
- | == what the datasheet tells us == | + | === what the datasheet tells us === |
The cells inside [[electrical: | The cells inside [[electrical: | ||
Line 143: | Line 143: | ||
| 10°C T <15°C | 0.2C | | 10°C T <15°C | 0.2C | ||
| 15°C T <45°C | 0.5C | | 15°C T <45°C | 0.5C | ||
- | | 45°C T <55°C | 0.2C | | + | | 45°C T <55°C | 0.2C | |
| >55°C | No charging allowed | | >55°C | No charging allowed | ||
- | == C rate at full charging power == | + | === C rate at full charging power === |
- | In secessus' | + | In secessus' |
- | == putting it all together == | + | === putting it all together |
- | Because his charge rate can reach **0.2C** he chose a warming | + | Because his charge rate can reach **0.2C** he chose a warming |