Configurations with no float (" | Configurations with no float (" | ||
- | - charge to the Absorption (" | + | - charge to the Absorption (" |
- **stop charging** | - **stop charging** | ||
- | - until voltage falls to the rebulk (" | + | - until voltage falls to the rebulk (" |
- repeat | - repeat | ||
- | The fall to reBulk looks like the transition to Vfloat described above. In both cases the controller makes no (or practically no) power until the lower setpoint is reached. | + | The fall to reBulk looks like the transition to Vfloat |
=== Renogy confusion === | === Renogy confusion === | ||
- | By default Renogy Li profiles work this way, and cause much concern for Renogy users who have not read their manuals and/or who do not understand | + | By default Renogy Li profiles work this way, and cause much concern for Renogy users who have not read their manuals and/or who are not familiar with how solar charge controllers / chargers work. [The required information is present [[https:// |
* **Rover series** - the table on page 37 of [[https:// | * **Rover series** - the table on page 37 of [[https:// | ||
Line 145: | Line 145: | ||
* the manual does not state the 13.2v boost return setpoint [an egregious error - secessus] | * the manual does not state the 13.2v boost return setpoint [an egregious error - secessus] | ||
- | Users uncomfortable with this behavior can set up the USER profile to meet their needs, including defining [[electrical: | + | Users uncomfortable with this behavior can set up the USER profile to meet their needs, including defining [[electrical: |