Solar charge controller setpoints
Solar charge controller, converter, and DC-DC charging behavior is guided by setpoints, which are settings stored in the controller. They may or may not be configurable by the user.
The two most important setpoints for battery life and performance are charging voltages: Absorption voltage and Float voltage, discussed below.
charging setpoints
Charging setpoints are configured in accordance with the battery manufacturer's recommendations.1) These recommendations are published in manuals, spec sheets, corporate blogs, etc. For example, Trojan's recommendations for charging their T-105 AGM batteries looks like this:
Absorption voltage (Vabs) - the voltage the battery bank is held at until
Absorption stage2) is
completed. In this case the recommendation is 14.4v.
Completed absorption means your lead batteries are fully charged.
3)
Float voltage (Vfloat) - the voltage the battery bank is held at during
Float. In this case the recommendation is 13.5v.
Equalization voltage (Vequal) - the voltage the battery bank is held at during
Equalization. In this case the recommendation is 15v+.
Temperature compensation - how the voltage setpoints are
adjusted for temperature. While this is sometimes configurable, the compensation factor is close enough between manufacturers that it is often left at the default.
endAmps - the amount of current (or percentage of capacity) accepted by the battery in late Absorption that indicates it's appropriate to Float. In the lower-right of
this graph Trojan shows it as
C/200:
4) Also see
absorption duration below.
Simpler charge controllers may only have preconfigured presets like “FLOODED” or “AGM” and don't let you set exact setpoints. If this is the case pick the closest preset to the recommendations5) and understand you will likely not get full performance or lifetime from the battery bank. Shunt controllers typically have only one configurable voltage setpoint. The simplest controllers may have no battery settings at all, and may or may not publish what those mystery settings are.
Less common setpoints:
Absorption duration - the amount of time Vabs will be held until dropping to Vfloat. May be used instead of or in addition to any
endAmps above.
endAmps is more precise but can be tricky to measure, as
loads or
multiple controllers can obscure the true level of current being accepted by the battery.
Absorption restart - voltage (or duration) at which Absorption stage after failing to maintain Vfloat. Sometimes called rebulk or reboost.
Equalization duration - the amount of time the controller will hold Vequal.
Equalization frequency - the number of days between equalization. 30 days is typical.
load setpoints
Only present on controllers with LOAD outputs.
non-setpoint settings
Maximum charge rate: While maximum charge rates normally are immaterial to solar charging
7), Trojan specfies a maximum of
C/5, or 1/5th of the battery's capacity in Ah for this flooded example. C/3 is a common max for AGM. Lithium max charge is typically stated as C/2 for maximum life.
Minimum charge rate: not stated in our example, but typical minimum charging values are ~C/10 for flooded lead batteries, and ~C/5 for AGM. Lithium does not have a practical minimum rate so is not damaged by weak charging.