Table of Contents

C notation

C notation is used to express the relationship of a bank's capacity to charge/discharge current. Example: a 20A current into or out of a 100Ah bank is 0.2C (20A / 100Ah). The same calculation could be made with W/Wh since it's about the relationship between the two and not any specific unit of measurement.

This relationship can also be described as a fraction; the above would be C/5.

Note: most deep cycle manufacturer's rate capacity at C/20 (0.05C), due to Peukert effect on lead chemistries (see below).1). In other words, a 100Ah battery will deliver 100A with a 5A load over 20 hours.

Examples

Assuming a 200Ah bank:

other than 20hr rates

Because of the Peukert effect, lead bank measured capacities are strongly affected by dicharge rate. Sample data below is for flooded lead acid.2) C/20 capacity is multiplied by the factor below to find projected capacity at given discharge rates.

Example: our battery is rated at 100Ah when drained at 5A over 20 hours. If it is drained at 20A in 5 hours it will have an observed capacity of 70Ah (100Ah x .7).

1 Hour = .3
2 Hour = .5
3 hour = .6
4 hour = .65
5 hour = .7
6 hour = .75
8 hour = .8
10 hour = .85
12 hour = .9
16 hour = .95
20 hour = 1
24 hour = 1.05
36 hour = 1.1
72 hour = 1.25
100 hour = 1.303)

1)
Lithium doesn't not have a significant Peukert effect. Capacity measured by C/20 and by amp-counting will be nearly identical
2)
Due to lower internal resistance AGM is less affected by discharge rate and lithium is barely affected at all.
3)
vhttps:www.solarpaneltalk.com/forum/off-grid-solar/batteries-energy-storage/11731-peukert-law-batteries-and-you#post11731))