No, you can use any panel that meets spec. Consult the power station's solar ("PV") input specs and buy panel[s] whose output specs are within the PS' stated limits. For the purposes of this section we will use these actual specs for reference:
12v-45v, 10A
In this case
Sometimes the PS will have more information that tells us the voltage range where the panels can be run for maximum power:
MPPT range 15v-38v
This tells us that Vmp can be anywhere from 15v to 38v. Outside that range (but within the absolute limits above) the panels will make something but not maximum power.
Power station solar input docs give a Max Wattage spec with a voltage range and usually a current limit.
12v-45v, 10A
Watts = Volts x Amps, so the Vmp of our panel3) will dictate what we can get at that 10A limit:
Sometimes no current limit is stated and we have to back into it:
12v-45v, 500w
In this case the 500w will be attainable at at 45v, and the current limit is likely 11.11A (500w / 45v). The panel's Voc cannot exceed 45v.
you can run the DC output to a bus or fuse box to split the connection. The total current must be within the PS' DC ouput limit; see below.
There is no easy/cheap way around this. Buy a PS that has sufficient specs to meet your needs.
and if theres a way to have it always charge at 100w?
That depends on the cause, the power station, and one's ability/willingness to DIY a solution. And it can't be always, just more of the time.4)
… then fix the connection. Clean/adjust/replace as needed. Anderson PowerPoles are a common upgrade.
If the wall charger output is 100w you could even run a cheap inverter from the ciggy port and plug the wall charger into that. It would be inefficient but we don't really care because the numbers are small and alternator output relative massive. This approach would work because the wall charger's output is usually at the higher end of the SG's DC input voltage limit.
If the wall charger >100w5) you could get more consistent charging by boosting/regulating voltage up as described above. So if the wall charger runs at 15v one might boost the outlet's voltage to 15v.
If it's a larger PS that can accept 100s of watts it might be easier to run a semi-DIY relay/inverter setup.